subject
Engineering, 03.01.2020 04:31 rbgrh8183

An air-conditioning system operates at a total pressure of 95kpa and consists of a heating section and a humidifier that supplies wet steam (saturated water vapor) at 100°c. air enters the heating section at 10°c and 70% relative humidity at a rate of 35 m^3/min, and it leaves the humidifying section at 20°c and 60 percent relative humidity. determine:

(a) the temperature and relative humidity of air when it leaves the heating section.

(b) the rate of heat transfer in the heating section.

(c) the rate at which water is added to the air in the humidifying section.

Answers

ansver
Answer from: mpete1234567890

The temperature and relative humidity when it leaves the heating section = T2 = 19° C and ∅2 = 38%

Heat transfer to the air in the heating section = Qin = 420 KJ/min

Amount of water added =  0.15 KG/min

Explanation:

The Property of air can be calculated at different states from the psychometric chart.

At T1 = 10° C  and ∅ = 70%

h1 = 87 KJ/KG of dry air

w1 = 0.0053  kg of moist air/ kg of dry air

v1 = 0.81 m^3/kg

AT T3 = 20° C ,  3  ∅ = 60%

h3 = 98 KJ/KG of dry air

w3 = 0.0087 kg of moist air/ kg of dry air

The moisture in the heating system remains the same when flowing through the heating section hence, (w1 = w2)

The mass flow rate of dry air,

m1 = V'1/V1 = 35/0.81

m1 = 43.21 kg/min

By balancing the energy in heating section we get:

mwhw + ma2h2 = mah3

(w3 -w2)hw + h2 = h3

h2 = h3 - (w3 -w2)hw @ 100 C

Hence, hw = hg @ 100 C and w2 = w1

h2 = h3 - (w3 -w2) hg @ 100 C

h2 = 98 - ( 0.0087 - 0.0053) * 2676

h2 = 33.2 KJ/KG

The exit temperature and humidity will be,

T2 = 19.5° C and  2 ∅ = 37.8%

(b) Calculating the transfer of heat in the heating section

Qin = ma(h2 -h1) = 43.21(33.2 - 23.5)

Qin = 420 KJ/min

(c) Rate at which water is added to the air in the humidifying section,

mw = ma(w3 - w2) = (43.2)(0.0087 - 0.0053)

mw = 0.15 KG/min

ansver
Answer from: Quest

visit this site

explanation:

ansver
Answer from: Quest
Idon’t do engeneering classes sorry

Other questions on the subject: Engineering

image
Engineering, 04.07.2019 18:10, Strick1530
Which of the following components of a pid controlled accumulates the error over time and responds to system error after the error has been accumulated? a)- proportional b)- derivative c)- integral d)- on/off.
Answers: 2
image
Engineering, 04.07.2019 18:10, selenamr
Ifa component is made of two or more materials with different modulus of elasticity (e), it is called a composite member and we calculate the factor·n". mention the formula for calculating n". also, ifn> 1, explain what will happen to the 1. transformed. gi) ifn 1, what will happen to the material when transformed material when
Answers: 1
image
Engineering, 04.07.2019 18:20, AnonymousLizard52303
A2-m rigid tank initially contains saturated water vapor at 100 kpa. the tank is connected to a supply line through a valve. steam is flowing in the supply line at 600 kpa and 300 c. the valve is opened, and steam is allowed to enter the tank until the pressure in the tank reaches the line pressure, at which point the valve is closed. a thermometer placed in the tank indicates that the temperature at the final state is 200°c. determine (a) the mass of steam that has entered the tank (b) the amount of heat transfer.
Answers: 3
image
Engineering, 04.07.2019 18:20, rocio5649
Amixture of slurry and mud is to be pumped through a horizontal pipe of diameter 500 mm. the fluid behaves as a bingham plastic with a yield stress of 30 pa and viscosity 0.04 pa. s. describe the effects of the shear stress through a transverse section of the pipe by plotting the variation in shear stress and velocity profile: (i) just before the slurry starts to move (ii) as the slurry flows when the pressure gradient is double that in part (i)
Answers: 3
You know the right answer?
An air-conditioning system operates at a total pressure of 95kpa and consists of a heating section a...

Questions in other subjects:

Konu
Mathematics, 02.07.2019 22:40